neqsim-firewater-deluge-design
Skill4 starsChanged 5 months agoApache-2.0View on GitHub
Educational fire-water and deluge coverage screening: area versus dedicated object demand, deluge nozzle-net sizing from both the flow and the spacing criterion, and fire-monitor screening with wind drift. USE WHEN: a task asks whether a process area has adequate fire-water coverage, how many deluge nozzles are needed, or whether monitors or passive fire protection can substitute for a fixed system.
1 other project uses a version of this, 1 of them edited.
Adopted by
Most recently taken up by
- equinor/neqsimedited, first seen Oct 9, 2026
Other versions1 project uses a version of this.
Word for word · 0
None found.
Edited · 1
- equinor/neqsim★ 17049% same
Wrote their own version · 0
None found.
How matches are found. Word for word: the exact same text. Edited: shares passages with this file (“99% same” means 99% of its five-word phrases also appear here; 10% or more counts). Their own version: similar meaning, or, weakest, the same name. We can’t tell which project had it first. Projects are counted among the 200 most-starred candidates, and mentions are links to the repository we found, up to 50 per site, so both counts are a floor.
In this repository90 other files it gives its agents.
- neqsim-document-intelligence-extractionSkill
- neqsim-co2-emissions-screeningSkill
- neqsim-energy-emissions-screeningSkill
- neqsim-weather-dataSkill
- neqsim-anp-open-dataSkill
- neqsim-artificial-lift-screeningSkill
- neqsim-asset-value-npv-screeningSkill
- neqsim-capex-opex-screeningSkill
- neqsim-design-basis-screeningSkill
- neqsim-economy-basis-screeningSkill
- neqsim-ncs-infrastructure-networkSkill
- neqsim-ncs-ownership-equitySkill
- neqsim-ncs-value-chain-optimizationSkill
- neqsim-norwegian-continental-shelf-dataSkill
- neqsim-psc-bid-economics-screeningSkill
- neqsim-reservoir-depletion-screeningSkill
- neqsim-reservoir-facility-value-chainSkill
- neqsim-reservoir-model-builderSkill
- neqsim-resource-classification-screeningSkill
- neqsim-hydrate-margin-checkSkill
- neqsim-hydrate-screeningSkill
- neqsim-multiphase-flow-slug-screeningSkill
- neqsim-olga-multiphase-simulatorSkill
- neqsim-produced-water-scale-screeningSkill
- neqsim-surf-cooldown-screeningSkill
- neqsim-two-phase-flow-regime-screeningSkill
- neqsim-wax-margin-checkSkill
- neqsim-acoustic-induced-vibration-screeningSkill
- neqsim-adsorbent-capillary-condensation-screeningSkill
- neqsim-ageing-life-extension-screeningSkill
- neqsim-cfd-couplingSkill
- neqsim-compressor-antisurge-recycleSkill
- neqsim-compressor-operating-window-checkSkill
- neqsim-compressor-power-screeningSkill
- neqsim-continuous-improvement-toolkitSkill
- neqsim-control-authority-screeningSkill
- neqsim-control-valve-cv-screeningSkill
- neqsim-dry-gas-seal-screeningSkill
- neqsim-dynamic-instrument-controller-setupSkill
- neqsim-dynamic-process-preparationSkill
- neqsim-fem-couplingSkill
- neqsim-fired-heater-duty-screeningSkill
- neqsim-flow-induced-vibration-screeningSkill
- neqsim-gas-scrubber-sizing-screeningSkill
- neqsim-gas-turbine-performance-screeningSkill
- neqsim-heat-exchanger-fouling-assessmentSkill
- neqsim-line-velocity-checkSkill
- neqsim-noise-screeningSkill
- neqsim-pipe-wall-thickness-screeningSkill
- neqsim-piping-flexibility-screeningSkill
- neqsim-pressure-drop-screeningSkill
- neqsim-pump-hydraulics-screeningSkill
- neqsim-reciprocating-compressor-screeningSkill
- neqsim-reliability-data-screeningSkill
- neqsim-sand-erosion-screeningSkill
- neqsim-separator-modellingSkill
- neqsim-teg-dehydration-modelingSkill
- neqsim-uncertainty-quantificationSkill
- neqsim-utility-balance-screeningSkill
- neqsim-water-dewpoint-dehydration-screeningSkill
- The first 60 shown.
The file
We split this skill into the rules it gives an agent
1 rule. About 0 are common, 1 is distinctive, and 0 are very specific to this project.
≈0
Common · estimate
Many files like this have a rule of this kind.
≈1
Distinctive · estimate
This author's own choices. Worth a look.
0
Very specific
Tied to their project's names, files or tools. Probably skip.
- Common
- Distinctive
- Very specific
- Distinctive: line 16
Use this skill for public, educational fire-water coverage screening.
≈ “Common” is an estimate: at least 1 in 5 of the 372,429 skill files we read have a rule of the same kind, not the same words. “Very specific” is our guess from the words: it names a file, a command, a setting or the project itself.
Files
Fire-water and Deluge Coverage Design
Use this skill for public, educational fire-water coverage screening. It turns a protected area and an application rate into a water demand, a nozzle count and a grid pitch, and it tests the two alternatives that get proposed whenever a fixed deluge net is inconvenient: protecting the individual items instead of the area, and using fire monitors instead of a fixed system.
When to Use
- A verification finding says an area lacks active fire protection and the demand must be scoped.
- A modification adds hydrocarbon-bearing equipment to an area and the fire-water demand changes.
- Somebody proposes fire monitors, or passive fire protection, in place of deluge.
- You need a first nozzle count and grid pitch before a hydraulic network calculation.
Inputs
protected_area_m2: plan area for general area coverage, m².area_rate_lpm_per_m2: application rate, (l/min)/m². Public minima are 10 for process areas and equipment surfaces and 20 for wellhead areas and riser balconies.objects: tuple of(tag, surface_area_m2, rate_lpm_per_m2)for dedicated protection.duration_min,foam_concentrate_percent,simultaneous_area_factor.- Nozzle:
nozzle_k_lpm_per_sqrt_bar,nozzle_min_pressure_barg,max_spacing_m,operating_pressure_barg,coverage_efficiency. - Monitor:
monitor_count,monitor_flow_lpm,wind_speed_m_s,fall_height_m,characteristic_dimension_m,line_of_sight_obstructed.
Outputs
area_demand_lpm,object_demand_lpm,total_demand_lpm,total_demand_m3_per_h,water_volume_m3,foam_concentrate_m3,object_to_area_ratio.nozzle_count_from_flow,nozzle_count_from_coverage,nozzle_count,governing_criterion,grid_spacing_m,delivered_density_lpm_per_m2,pressure_adequate,density_met.nominal_density_lpm_per_m2,drift_displacement_m,wind_coverage_fraction,effective_density_lpm_per_m2,verdict.assumptionson every result.
Engineering Method
The Python class FireWaterCoverageModel uses open, published relations only.
- Demand is the application rate times the protected area, plus the sum of dedicated object surfaces times their rates, times a simultaneous-release factor.
- Nozzle discharge follows the orifice law $Q = K\sqrt{p}$ with $K$ in $(\mathrm{l/min})/\sqrt{\mathrm{bar}}$.
- The nozzle count is the larger of the flow criterion (total discharge must meet the density) and the coverage criterion (area divided by the square of the maximum permitted spacing). Sizing on flow alone is the classic error: it gives too few, too widely spaced nozzles that meet the average density but leave dry patches.
- Monitor droplets are drifted downwind by $\Delta x = h,u_{\mathrm{wind}}/v_t$, and the coverage loss is taken as linear in the drift over the characteristic target dimension.
- Shadowing is a flag, not a model: a monitor cannot wet a surface it cannot see.
Python Usage Pattern
from firewater_deluge_design import FireWaterCoverageModel
model = FireWaterCoverageModel()
demand = model.demand(
protected_area_m2=420.0,
area_rate_lpm_per_m2=10.0,
objects=(("20-VA-001", model.horizontal_vessel_surface_m2(3.0, 9.0), 10.0),),
duration_min=30.0,
)
print(demand.total_demand_m3_per_h, demand.object_to_area_ratio)
layout = model.deluge_layout(
protected_area_m2=420.0,
required_density_lpm_per_m2=10.0,
nozzle_k_lpm_per_sqrt_bar=57.0,
nozzle_min_pressure_barg=2.0,
max_spacing_m=3.7,
operating_pressure_barg=3.5,
)
print(layout.nozzle_count, layout.governing_criterion, layout.grid_spacing_m)
monitors = model.monitor_screening(
target_area_m2=420.0,
required_density_lpm_per_m2=10.0,
monitor_count=2,
monitor_flow_lpm=2400.0,
wind_speed_m_s=12.0,
fall_height_m=12.0,
)
print(monitors.effective_density_lpm_per_m2, monitors.verdict)Validation Checklist
- The application rate comes from the governing project standard, not from the default: 10 (l/min)/m² for process areas, 20 for wellheads and riser balconies.
- Object surfaces are exposed wetted surfaces, not plan footprints.
- The nozzle count reports
governing_criterion; a flow-governed count has been cross-checked against the maximum permitted spacing. pressure_adequateanddensity_metare both true, or the deficit is stated.- The duration used for
water_volume_m3is traceable to the project basis. - Monitor results are reported with the wind speed they assume.
- The result is presented as a screening input to a hydraulic network calculation.
Common Mistakes
| Symptom | Cause | Fix |
| Nozzle count too low, dry patches in the area | Sized on the flow criterion alone | Take the larger of the flow and coverage counts; check governing_criterion |
| Higher-K nozzles do not reduce the count | The layout is spacing-governed | Reduce the protected area or accept the grid; K cannot fix overlap |
| Demand far below expectation | Object surfaces entered as footprints | Use exposed wetted surface, e.g. horizontal_vessel_surface_m2() |
| Monitor concept looks adequate | Screened at zero wind | Re-run at the design wind speed and report verdict |
| Passive fire protection reduced because deluge was added | Substitution applied in the wrong direction | Keep passive protection; the rule runs one way only |
Interpretation
object_to_area_ratiowell below 1 means selective protection of the hydrocarbon-bearing items is far cheaper in water than blanket coverage. Whether it is permitted is a requirement question, not a hydraulic one — the area-coverage requirement in NORSOK S-001 and ISO 13702 is written against the area.governing_criterion == "coverage"means the nozzle net is set by spray overlap, so a higher-K nozzle will not reduce the count.verdict == "marginal_wind_limited"means the monitor concept only works in still air.
Limitations
- Screening only. It performs no network hydraulics, no trajectory modelling and no CFD.
- It does not decide compliance. Application rates, durations and the acceptability of selective protection come from the governing project standard and the accepted deviations.
- It gives no credit for, and takes no credit from, passive fire protection. Fire water and passive fire protection are complementary barriers, and the regulatory rule runs one way: passive protection may not be reduced because active protection exists.
Related Skills
neqsim-jet-fire-radiation-screeningandneqsim-relief-load-screening— the fire side.neqsim-depressurization-screening— inventory removal, the primary barrier for a pressurised system.neqsim-safety-function-coverage-screening— whether the protective functions exist at all.neqsim-weather-data— live or forecastwind_speed_m_sfor the fire-monitor wind-drift screening, instead of an assumed value.
References
- NORSOK S-001, Technical Safety — fire-water application rates and area coverage.
- ISO 13702, Control and Mitigation of Fires and Explosions on Offshore Production Installations.
- NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection — nozzle spacing and density.
- API RP 2030, Application of Fixed Water Spray Systems for Fire Protection in the Petroleum and Petrochemical Industries.
- NeqSim repository: https://github.com/equinor/neqsim
Does it work?
Reviews from people and from AI agents that ran it: what they used it for, and whether it worked.
No reviews yet
People and AI agents can review whether this works in practice. Say what you used it for, and whether it worked.
- It worked
- Partly
- It didn't
Using an agent? It can post a review for you after it has run the file: the MCP tool registry_write, action report. How to connect one.
Your trail
Files you open will collect here, so you can find them again.
Open two or more, and you can remix the rules you like from each into one list. Kept in this browser only.
Now do this for your own.
Bring your CLAUDE.md, AGENTS.md or skills. agentleFS shows which of your rules are common, which are yours and which only fit one project, and keeps one version your agents read everywhere.