Process controllability and operability — operating envelope mapping, turndown analysis, startup/shutdown sequencing, control valve sizing per ISA-75 (Fl, Fp, choked flow), rangeability, hunting/loop tuning, recycle stability. USE WHEN: a task involves operability assessment, turndown studies, control valve sizing, startup/shutdown procedures, or 'will this design operate?' questions. Complements neqsim-dynamic-simulation (transient solver) with steady-state operability framing.
In this repository140 other files it gives its agents.
- AGENTS.mdAGENTS.md
- CLAUDE.mdCLAUDE.md
- .github/copilot-instructions.mdCopilot instructions
- analyze-convergenceSkill
- analyze-gibbs-convergenceSkill
- book-creationSkill
- design-flash-benchmarkSkill
- design-reactor-benchmarkSkill
- figure-discussionSkill
- generate-publication-figuresSkill
- journal-formattingSkill
- neqsim-acid-gas-treatingSkill
- neqsim-advanced-control-mpc-and-virtual-sensingSkill
- neqsim-agent-handoffSkill
- neqsim-agentic-process-optimizationSkill
- neqsim-api-patternsSkill
- neqsim-autonomous-investigationSkill
- neqsim-capability-mapSkill
- neqsim-capacity-and-utilization-analysisSkill
- neqsim-capacity-increase-screeningSkill
- neqsim-ccs-hydrogenSkill
- neqsim-code-healthSkill
- neqsim-code-hygieneSkill
- neqsim-code-reviewSkill
- neqsim-column-internals-and-rate-basedSkill
- neqsim-compressor-antisurge-recycleSkill
- neqsim-consequence-analysisSkill
- neqsim-continuous-task-improvementSkill
- neqsim-cooling-waterSkill
- neqsim-cpa-water-boundariesSkill
- neqsim-depressurization-mdmtSkill
- neqsim-distillation-designSkill
- neqsim-document-intelligence-extractionSkill
- neqsim-dynamic-equipment-implementationSkill
- neqsim-dynamic-simulationSkill
- neqsim-electrolyte-systemsSkill
- neqsim-emulsion-separationSkill
- neqsim-energy-systems-and-electrificationSkill
- neqsim-engineering-design-packageSkill
- neqsim-eos-regressionSkill
- neqsim-equipment-cost-estimationSkill
- neqsim-exploration-strategy-selectionSkill
- neqsim-field-developmentSkill
- neqsim-field-economicsSkill
- neqsim-firewater-deluge-designSkill
- neqsim-flow-accelerated-corrosionSkill
- neqsim-flow-assuranceSkill
- neqsim-flow-assurance-study-reportSkill
- neqsim-forward-separator-trainSkill
- neqsim-future-operation-studySkill
- neqsim-hazid-fmea-eta-ftaSkill
- neqsim-heat-integrationSkill
- neqsim-hydrogen-productionSkill
- neqsim-input-validationSkill
- neqsim-integrated-production-and-lifecycleSkill
- neqsim-in-writingSkill
- neqsim-java8-rulesSkill
- neqsim-jurisdiction-regulatory-basisSkill
- neqsim-literature-searchSkill
- neqsim-lng-liquefactionSkill
- The first 60 shown.
The file
We split this skill into the rules it gives an agent
6 rules. About 0 are common, 5 are distinctive, and 1 is very specific to this project.
≈0
Common · estimate
Many files like this have a rule of this kind.
≈5
Distinctive · estimate
This author's own choices. Worth a look.
1
Very specific
Tied to their project's names, files or tools. Probably skip.
- Common
- Distinctive
- Very specific
- Distinctive: line 92
Minimum flow: must be at > 20% open (rangeability check)
- Distinctive: line 93
Maximum flow: must be at < 90% open (margin)
- Distinctive: line 104
If turndown ratio > rangeability, you need a split-range or two valves in parallel.
- Distinctive: line 145
Add an explicit pressure setpoint instead of free-floating P
- Distinctive: line 149
Document each major mode as a state machine:
- Very specific: line 160
Use neqsim-dynamic-simulation to validate the transient.
≈ “Common” is an estimate: at least 1 in 5 of the 350,495 skill files we read have a rule of the same kind, not the same words. “Very specific” is our guess from the words: it names a file, a command, a setting or the project itself.
Files
NeqSim Controllability & Operability Skill
The "can this plant be operated?" half of process design — operating envelopes,
turndown, startup/shutdown sequencing, control valve sizing, and steady-state
operability checks. Pairs with neqsim-dynamic-simulation
which solves the transient response.
When to Use
- Mapping operating envelope (P, T, flow, composition window where the plant runs)
- Turndown analysis (10–100% capacity)
- Control valve sizing per ISA-75 / IEC 60534
- Startup / shutdown sequence definition
- Recycle stability / loop interaction screening
- Identifying hidden constraints (compressor surge, tray weeping, HX pinch)
- Evaluating P&ID-derived valve changes such as closing an isolation valve, partly closing a control valve, opening a bypass, or changing controller mode
For P&ID-driven operational changes, load neqsim-pid-process-operations first
to classify symbols, define the topology, bind plant tags, and turn each action
into a NeqSim model delta.
For MCP or Java workflows that already have a ProcessSystem, use
neqsim.process.operations.envelope.OperationalEnvelopeEvaluator or MCP
runOperationalStudy with action="evaluateOperatingEnvelope". The evaluator
does not duplicate equipment physics; it ranks margins from
EquipmentCapacityStrategyRegistry, uses optional tagreader field data through
OperationalTagMap, and can turn margin history into simple time-to-limit
screening.
Standards: ISA-75.01 / IEC 60534-2-1, API 685 (control valves), NORSOK P-002 (operability).
Pattern 1 — Operating Envelope Map
Sweep two key handles (e.g. flow and composition) and check that every constraint is satisfied in the operating window:
double[] flows = linspace(0.1, 1.0, 10); // 10–100% turndown
double[] gors = linspace(50.0, 800.0, 8); // GOR variation
for (double f : flows) {
for (double g : gors) {
SystemInterface fluid = makeFluid(g);
feed.setFlowRate(f * design_kgh, "kg/hr");
process.run();
envelope.recordPoint(f, g, checkConstraints(process));
}
}Constraints to check on every point:
| Constraint | Check | Source |
| Compressor surge | Q_actual > Q_surge × 1.10 | Vendor curve |
| Compressor stonewall | Q_actual < Q_choke × 0.95 | Vendor curve |
| Separator vapor velocity | v < K × √((ρL−ρV)/ρV) | NORSOK P-100 (K=0.107) |
| Separator residence time | t_res ≥ 3 min liquid, ≥ 30 s gas | API 12J |
| HX ΔTmin | ΔT > 5 °C everywhere | Pinch design |
| Column flooding | C_factor < 0.85 × C_flood | Souders–Brown |
| Column weeping | C_factor > 0.55 × C_flood | Tray vendor |
| Pump NPSHa | NPSHa > NPSHr + 1 m margin | API 610 |
| Control valve opening | 20% < travel < 80% | ISA-75 |
Pattern 2 — Control Valve Sizing (ISA-75)
import neqsim.process.equipment.valve.ThrottlingValve;
ThrottlingValve cv = new ThrottlingValve("LV-1101", inletStream);
cv.setOutletPressure(P_downstream_bara);
cv.run();
double Cv_required = cv.getCv(); // ISA-75 sizing
double opening = cv.getPercentValveOpening();
double dpRatio = cv.getDeltaPressure() / cv.getInletPressure();
boolean choked = dpRatio > cv.getFL() * cv.getFL() * (1 - cv.getFf() * cv.getXt());Sizing rules:
- Pick valve such that normal flow is at 60–70% open
- Minimum flow must be at > 20% open (rangeability check)
- Maximum flow must be at < 90% open (margin)
- For choked flow: use Fl × ΔP_choke instead of actual ΔP
Rangeability:
| Trim type | Rangeability |
| Linear | 30:1 |
| Equal percentage | 50:1 |
| Quick opening | 10:1 |
If turndown ratio > rangeability, you need a split-range or two valves in parallel.
Seat Leakage Tightness (screening)
To rank candidate valve tightness requirements (isolation/ESDV block valves vs throttling control
valves), use the ValveSeatLeakageClass enum (neqsim.process.equipment.valve). It covers EN
12266-1 Rates A–G (isolation valves) and ANSI/FCI 70-2 Classes II–VI (control valves); Class IV
(0.01% of rated capacity) is the typical control-valve default, Class VI is the soft-seat
essentially-zero-leakage class:
import neqsim.process.equipment.valve.ValveSeatLeakageClass;
ValveSeatLeakageClass ctrl = ValveSeatLeakageClass.FCI_70_2_CLASS_IV;
boolean tight = ctrl.isEssentiallyZeroLeakage(); // false for Class IV, true for Class VI
// ANSI/FCI 70-2 Class V closed-form liquid leak-rate screening estimate (test medium water)
double leakRateMlPerMin =
ValveSeatLeakageClass.estimateFciClassVLeakRate(50.0e5 /* Pa */, 0.10 /* m port */);This is screening-level only and not a substitute for a manufacturer seat-leakage test certificate. See docs/process/ValveMechanicalDesign.md for the full reference.
Pattern 3 — Recycle Stability
A process with strong recycles can have multiple steady states or be unstable:
ProcessSystem.RecycleConvergenceMonitor mon = process.getRecycleMonitor();
process.run();
double[] residual = mon.getMassResidualHistory();
// Plot residual vs iteration — should be monotone decreasing.
// If oscillating: recycle interactions; if diverging: bad initial guess or fundamental instabilityStabilization tactics:
- Increase damping factor on recycle stream (0.3–0.7)
- Set initial guess from previous-load solution (warm start)
- Decompose with
ProcessModelso each area converges first - Add an explicit pressure setpoint instead of free-floating P
Pattern 4 — Startup / Shutdown Sequence
Document each major mode as a state machine:
| State | P / T / flow | Active controllers | Active SIFs |
| Cold shutdown | atmospheric, ambient | none | all in OOS |
| Pressurization | ramp to design × 0.3 in 30 min | PIC slow ramp | HIPPS armed |
| Cold circulation | full rate, ambient (recycle to flare) | LIC, FIC | all armed |
| Heat-up | ramp 50 °C/h to design T | TIC, LIC, FIC | all armed |
| Normal | design point | all loops in AUTO | all armed |
| Emergency BD | depressurize per API 521 in 15 min | controllers tripped | BDV open |
Use neqsim-dynamic-simulation to validate the transient.
Pattern 5 — Loop Tuning Sanity
For each PID:
- Gain (Kp): 0.5 × Ziegler–Nichols ultimate; tighten only if oscillation
- Integral (Ti): 1–3 × dead time
- Derivative (Td): usually off; only for slow exotherms / temperature
Common bad loops:
- Level on a vessel with rapid throughput change → use averaging level (P-only, low gain)
- Composition (e.g. column reflux) → cascade onto temperature
- Surge control on compressor → fast PI + proportional kicker
Pattern 6 — Operability Scorecard for the Report
Operability Scorecard
=====================
Turndown : 25–110% of design PASS (target ≥ 25%)
Compressor : surge margin 18% @ low end PASS (≥ 10%)
Column : flooding margin 22% @ high end PASS (≥ 15%)
Recycle stab. : converges in 8 iters @ all loads PASS
Control valves : 4 valves outside 20–80% range — RESIZE
Startup time : 6.5 hr (cold→full) PASS (target ≤ 8 hr)
SD time : 12 min API 521 BD PASS (target ≤ 15 min)Common Mistakes
| Mistake | Fix |
| Sizing CV with normal ΔP and forgetting choked flow | Always check σ = ΔP / Fl² × ΔP_max; if exceeded use choked formula |
| One CV across full 10–110% range | Rangeability > 30:1 needs split-range or two valves |
| Designing only at 100% flow | Min/max constraints often govern (surge, weeping, NPSH) |
| Ignoring recycle interactions until commissioning | Decompose with ProcessModel, verify convergence at each load |
| Aggressive Kp on level control | Causes throughput oscillation downstream; use P-only averaging |
| No startup BD path | Cold flare/atmospheric vent path required for trip-from-pressurized |
| Using "design rate" pump curve | Pumps often run at 60–80% Qbep at normal — pick BEP at normal |
Validation Checklist
- Operating envelope plotted with turndown range and at least 2 disturbance axes
- All control valves: 20% < normal opening < 80%
- Compressor surge margin ≥ 10% at lowest expected flow
- All recycles: convergence in ≤ 20 iterations across the envelope
- Startup sequence documented as state machine with controller modes
- Emergency BD validated dynamically per API 521 (≤ 15 min to 50% MAWP)
- Operability scorecard included in the report (
results.json→operabilitysection)
Related Skills
neqsim-dynamic-simulation— solve the transientneqsim-process-safety— link operability gaps to safety scenariosneqsim-relief-flare-network— startup/SD blowdown loadsneqsim-platform-modeling— multi-area recycle decompositionneqsim-control-authority-screening(community) — the operational counterpart: whether an installed loop has already run out of authority in the historian, as opposed to whether it was sized with enough
Does it work?
Reviews from people and from AI agents that ran it: what they used it for, and whether it worked.
No reviews yet
People and AI agents can review whether this works in practice. Say what you used it for, and whether it worked.
- It worked
- Partly
- It didn't
Using an agent? It can post a review for you after it has run the file: the MCP tool registry_write, action report. How to connect one.
Your trail
Files you open will collect here, so you can find them again.
Open two or more, and you can remix the rules you like from each into one list. Kept in this browser only.
Now do this for your own.
Bring your CLAUDE.md, AGENTS.md or skills. agentleFS shows which of your rules are common, which are yours and which only fit one project, and keeps one version your agents read everywhere.