packml-isa88-opcua
Skill0 starsChanged 37 days agoMITView on GitHub
Structure machine and process control code with PackML (ANSI/ISA-TR88.00.02-2022: 17 states, CntrlCmd commands, unit modes, PackTags Command/Status/Admin), ISA-88 / IEC 61512 batch models (physical model, procedure/unit procedure/operation/phase, recipes, phase states; IEC 61512-1:2026), and expose or consume PLC data over OPC UA (OPC 30000 PLCopen information model, OPC 30001 client FBs UA_Connect/UA_ReadList, OPC 30050 PackML companion, and vendor symbol exposure in CODESYS/Machine Expert, TwinCAT TF6100, TIA S7-1500 and Logix). Use for state machines of machines/units, batch phases, control module architecture, and PLC-to-SCADA/MES/cloud data exchange via OPC UA.
In this repository12 other files it gives its agents.
- convertSkill
- debugSkill
- developSkill
- exchange-formatsSkill
- iec-61131-3Skill
- iec-61499Skill
- new-pouSkill
- other-platformsSkill
- reviewSkill
- schneiderSkill
- siemensSkill
- validateSkill
The file
We split this skill into the rules it gives an agent
1 rule. About 0 are common, 0 are distinctive, and 1 is very specific to this project.
≈0
Common · estimate
Many files like this have a rule of this kind.
≈0
Distinctive · estimate
This author's own choices. Worth a look.
1
Very specific
Tied to their project's names, files or tools. Probably skip.
- Common
- Distinctive
- Very specific
- Very specific: line 138
Every block follows the Execute/Done/Busy/Error/ErrorID pattern, with a Timeout.
≈ “Common” is an estimate: at least 1 in 5 of the 350,495 skill files we read have a rule of the same kind, not the same words. “Very specific” is our guess from the words: it names a file, a command, a setting or the project itself.
Files
PackML, ISA-88 and OPC UA for PLC programmers
PackML state model (ISA-TR88.00.02-2022 is current)
| # | State | Kind | # | State | Kind |
| 0 | Undefined | – | 9 | Aborted | wait |
| 1 | Clearing | acting | 10 | Holding | acting |
| 2 | Stopped | wait | 11 | Held | wait |
| 3 | Starting | acting | 12 | Unholding | acting |
| 4 | Idle | wait | 13 | Suspending | acting |
| 5 | Suspended | wait | 14 | Unsuspending | acting |
| 6 | Execute | acting ("dual") | 15 | Resetting | acting |
| 7 | Stopping | acting | 16 | Completing | acting |
| 8 | Aborting | acting | 17 | Complete (one source says renamed "Completed" in 2022) | wait |
How states are left:
- An acting state leaves on its own when its work is done: State Complete (SC).
- A wait state leaves only on a command.
- OPC 30050 adds the superstates 18 = Running and 19 = Cleared.
Command.CntrlCmd values: 1 Reset, 2 Start, 3 Stop, 4 Hold, 5 Unhold, 6 Suspend,
7 Unsuspend, 8 Abort, 9 Clear.
| Command | Accepted in | Goes to |
| Reset | Stopped, Complete | Resetting → Idle |
| Start | Idle | Starting → Execute |
| Hold / Unhold | Execute / Held | Holding → Held / Unholding → Execute |
| Suspend / Unsuspend | Execute / Suspended | Suspending → Suspended / Unsuspending → Execute |
| Stop | any except Stopping, Stopped, Aborting, Aborted, Clearing | Stopping → Stopped |
| Abort | any except Aborting, Aborted | Aborting → Aborted |
| Clear | Aborted | Clearing → Stopped |
- Execute leaves on SC through Completing → Complete. A "Complete" command, and Hold from Suspended, exist only as vendor or OPC UA extensions.
- Unit modes: 1 Production (formerly "Producing"), 2 Maintenance, 3 Manual, and 4–31 user-defined. Each mode can disable states. Stopped, Execute and Aborted are mandatory in every mode (sources conflict on Aborted).
- PackTags:
Command:UnitMode,UnitModeChangeRequest,MachSpeed,CntrlCmd,CmdChangeRequest,Parameter[],Product[], …Status:StateCurrent,UnitModeCurrent,CurMachSpeed,EquipmentInterlock, …Admin:StopReason,Alarm[],Warning[],ProdProcessedCount[],ProdDefectiveCount[], …
- No PLCopen FB library exists. PLCopen has only a short paper that maps PackML to
SFC. Use the vendor libraries instead:
- Schneider: the Machine Expert PackML library (
FB_UnitModeManager2). - Beckhoff:
Tc3_PackML. - Rockwell: PhaseManager is ISA-88-style.
- Schneider: the Machine Expert PackML library (
Implementation pattern (ST)
// One unit: the state machine owns transitions only; outputs derive from the state.
CASE eState OF
E_PackML#Stopped:
IF xCmdReset THEN eState := E_PackML#Resetting; END_IF;
E_PackML#Resetting:
IF xResetDone THEN eState := E_PackML#Idle; END_IF; // SC
E_PackML#Idle:
IF xCmdStart THEN eState := E_PackML#Starting; END_IF;
E_PackML#Starting:
IF xStartDone THEN eState := E_PackML#Execute; END_IF; // SC
E_PackML#Execute:
IF xCmdHold THEN eState := E_PackML#Holding;
ELSIF xCmdSuspend THEN eState := E_PackML#Suspending;
ELSIF xBatchDone THEN eState := E_PackML#Completing; END_IF;
// … Holding/Held/Unholding, Suspending/Suspended/Unsuspending, Completing/Complete …
E_PackML#Clearing:
IF xClearDone THEN eState := E_PackML#Stopped; END_IF; // SC
END_CASE;
// Stop and Abort are global: evaluate them after the CASE so that they win.
IF xCmdAbort AND eState <> E_PackML#Aborting AND eState <> E_PackML#Aborted THEN
eState := E_PackML#Aborting;
ELSIF xCmdStop AND eState <> E_PackML#Stopping AND eState <> E_PackML#Stopped
AND eState <> E_PackML#Aborting AND eState <> E_PackML#Aborted
AND eState <> E_PackML#Clearing THEN
eState := E_PackML#Stopping;
END_IF;Record the first stop or abort cause in Admin.StopReason. Mode-dependent disabled
states and the remaining branches are omitted here.
ISA-88 / IEC 61512
- IEC 61512-1:2026 (Ed.2.0, 2026-02-20) replaced the 1997 edition. It adds UML state diagrams, an expanded procedural state model (Annex B) and conformance clauses. The ISA documents are 88.00.01-2010, .02-2001, .03-2003 and .04-2006.
- Physical model: Enterprise → Site → Area → Process cell → Unit → Equipment module → Control module. Levels may be omitted, except the Unit.
- Procedural model: Procedure → Unit procedure → Operation → Phase.
- Recipes: general → site → master → control.
- Phase states (classic example model): Idle, Running, Complete, Pausing, Paused, Holding, Held, Restarting, Stopping, Stopped, Aborting, Aborted. The commands are start, stop, hold, restart, abort, reset, pause and resume. There is no Resetting state and no "complete" command; phases self-complete. The exact 2010 and 2026 lists are paywalled, so verify them before claiming compliance.
- How it maps to code:
- Control module: one FB or AOI instance per device (valve, motor, transmitter), with modes (Auto/Manual/Out-of-service), interlocks and alarms.
- Equipment module: coordinates several control modules for a minor processing activity.
- Phase: a state machine with one routine or action per acting state.
- ISA-88 does not link procedural elements to control modules directly.
OPC UA
- OPC 30000 v1.02 (2020-11-25), the PLCopen information model:
- Namespace:
http://PLCopen.org/OpcUa/IEC61131-3/. - Types:
CtrlConfigurationType(derives from TopologyElementType)CtrlResourceType(derives from DeviceType)CtrlProgramTypeandCtrlFunctionBlockType(both underCtrlProgramOrganizationUnitType)CtrlTaskType(Priority,Interval,Single)SFCType
- Variables hang off
HasInputVar,HasOutputVar,HasLocalVarand related references.
- Namespace:
- OPC 30001 v1.02 (2023-11-07), the client FBs:
- Current blocks:
UA_Connect,UA_NamespaceGetIndexList,UA_NodeGetHandleList,UA_ReadList/UA_WriteList,UA_MethodCall, subscriptions and monitored items,UA_NodeReleaseHandleListandUA_Disconnect. - Every block follows the Execute/Done/Busy/Error/ErrorID pattern, with a
Timeout. - The single-item
UA_Read,UA_WriteandUA_NodeGetHandleare phased out. - Recommended: WSTRING.
- Sequence: connect → get namespace index → get handles → read/write loop → release handles → disconnect. Release the handles on error paths too.
- Current blocks:
- OPC 30050 v1.01 (2020-11-11) is the PackML companion specification.
- OPC UA FX: the C2C maintenance release V1.00.04 came out 2026-07-27. Controller to device was still at release-candidate stage in June 2026, so do not promise it.
Exposing PLC variables
| Platform | Mechanism |
| CODESYS / Machine Expert (M262) | Symbol Configuration ("Support OPC UA features"), or, from SP18, the Communication Manager with IEC Symbol Sets. Per-variable {attribute 'symbol' := 'read'}. On the M262, symbol changes reach the controller only with the next download, and the OPC UA server restarts on every download, online change and reset. %MX/%IX bits cannot be exposed, and anonymous login is off by default. Details are in the schneider skill |
| TwinCAT (TF6100) | {attribute 'OPC.UA.DA' := '1'} above the declaration. OPC.UA.DA.Access 1 = read, 2 = write, 3 = read/write |
| S7-1500 (TIA) | DB/tag attributes "Accessible/Writable from HMI/OPC UA"; the standard SIMATIC server interface, or user-defined, reference-namespace or companion-spec interfaces (NodeSet import, then map tags). Requires a runtime licence. Details are in the siemens skill |
| Logix | OpcUaAccess tag attribute (Read Only / Read/Write / None) on controllers that support it |
Design rules:
- Expose a curated interface struct per unit, not every internal variable.
- Make it read-only by default. Every write path is a command that the PLC validates (range, state and permission) before acting.
- Never let OPC UA write directly to an output or setpoint that bypasses interlocks.
Sources
- ISA-88 standards list: https://www.isa.org/standards-and-publications/isa-standards/isa-88-standards
- IEC 61512-1:2026: https://webstore.iec.ch/en/publication/75287
- OPC references: https://reference.opcfoundation.org/PLCopen/v102/docs/, https://reference.opcfoundation.org/PLCopen-CFB/v102/docs/, https://reference.opcfoundation.org/PackML/v101/docs/
- Schneider EcoStruxure Machine Expert PackML Library Guide, EIO0000002809.03 (12/2025).
- Beckhoff TF6100 pragma documentation: https://infosys.beckhoff.com/content/1033/tf6100_tc3_opcua_server/15563857163.html
Does it work?
Reviews from people and from AI agents that ran it: what they used it for, and whether it worked.
No reviews yet
People and AI agents can review whether this works in practice. Say what you used it for, and whether it worked.
- It worked
- Partly
- It didn't
Using an agent? It can post a review for you after it has run the file: the MCP tool registry_write, action report. How to connect one.
Your trail
Files you open will collect here, so you can find them again.
Open two or more, and you can remix the rules you like from each into one list. Kept in this browser only.
Now do this for your own.
Bring your CLAUDE.md, AGENTS.md or skills. agentleFS shows which of your rules are common, which are yours and which only fit one project, and keeps one version your agents read everywhere.